Module with 4 dry contact inputs, connected to KNX, in DIN rail format and compact (1 module). Mod'nX allows you to connect your technical alarms, OF/SD of your electrical panels, etc... to its inputs and to find them on your home automation supervision or BMS. Each NO or NC input can periodically emit a presence or absence of alarm, thus ensuring a guaranteed operation of the system
In combination with other products from our range, you can create a real decentralised technical alarm system. Easy to deploy and intuitive to use. It can be stand-alone or connected. The alarms are visual via a LED indicator display, and audible with a personalized message for each alarm via a loudspeaker
Combined with the Kloud'nX, you can monitor or be notified of alarms connected to the Mod'nX from your smartphone and keep an alarm history
It is the only KNX 4 binary input module that takes a single DIN rail module. Economical, it allows easy recovery (OF / SD / TA / TS)* in a small footprint with minimal wiring.
Combined with the products in the Can’nX range, the whole system becomes a real stand-alone or integrated technical alarm system, with advanced and connected functions: push, notification, broadcasting of sound and visual alarms.
Here are two additional functions that will allow you to anchor our product on all your KNX installations:
Autonomous or Connected
It is important today that certain technical alarms are processed immediately by the home automation system and that the customer is notified. Circuit breaker lowered, differential tripped, high level of a tank, fire, flooding…just as much essential information for your customer’s peace of mind. You can systematically offer our Secu’nX bundle connected to your home automation or simply pre-programmed to make it autonomous.
Monitoring & Notifications
Through your cloud interface, you can very easily create graphs to monitor and notify alerts on your smartphone, but also log certain alerts.
+++ Input characteristics
Signal voltage: supplied by the pushbutton interface. approx. 29 VDC (bus voltage) when the contact is open
Signal current: when contact is closed: 0.2 mA dc per channel when closing: 0.1 A pulse
Signal delay: 50 ms including bounce time
Input signal duration: min. 50ms
+++ Output characteristics
Signal voltage: supplied by the pushbutton interface. approx. 4.7Vdc, 1.9kOhm resistor (integrated)
Current: When the output is short-circuited, the current is about 2.5mA
+++ Technical data
Small footprint 1 DIN rail module, 13.58mm
KNX TP, S-Mode (ETS), 30V, 5mA, all channels as input: 6mA, all channels as output: 14mA
Power supply: Bus voltage: via KNX/EIB bus line
Operating temperature : – 5 – + 45 °C
Dimensions: 90 x 11mm, depth 57mm
2 years warranty
Cookie | Duration | Description |
---|---|---|
cookielawinfo-checkbox-analytics | This cookie is set by the GDPR Cookie Consent plugin. The cookie is used to store user consent for cookies in the “Analytics” category. | |
cookielawinfo-checkbox-functional | The cookie is set by the GDPR cookie consent to record user consent for cookies in the “Functional” category. | |
cookielawinfo-checkbox-necessary | This cookie is set by the GDPR Cookie Consent plugin. Cookies are used to store user consent for cookies in the "Necessary" category. | |
cookielawinfo-checkbox-others | This cookie is set by the GDPR Cookie Consent plugin. The cookie is used to store user consent for cookies in the "Other. | |
cookielawinfo-checkbox-performance | This cookie is set by the GDPR Cookie Consent plugin. The cookie is used to store user consent for cookies in the "Performance" category. | |
viewed_cookie_policy | The cookie is set by the GDPR Cookie Consent plugin and is used to store whether or not the user has consented to the use of cookies. It does not store any personal data. |
Bonjour! Vous avez une question sur nos produits ? Cliquez ci-dessous et connectez-vous à l'un de nos professionnels sur whatsapp.
Nous vous répondrons rapidement et en personne 🙂